Methane transmitter - ATEX zone 1
                      
                    
	 
	
	 
	Gas concentration transmitter with 4÷20 mA current output (three wires),0…100% L.E.L., designed for the detection of methane. The device is made of ATEX approved metal case with Ex d protection mode,carrying the electronic board and the gas sensor properly protected with a sintered filter located in the lower side of the case itself. The appliance is to be installed in ATEX zone 1. It can be connected to following control panels:
	- 
		RGY 000 MBP4 (with 4 zones)
- 
		RGY S00 MBP4 (with 4 zones,RS232 output)
- 
		RXA 01M (with 8 zones)
	 
	Technical features
	 
	
		
			| Power supply | : | 12…24 V |  | 
		
			| Output | : | 4÷20 mA |  | 
		
			| Sensor type | : | Catalytic (CESI OI ATEX 066U approval) |  | 
		
			| Housing | : | Ex d protected (FTZU 05 ATEX 0262U approval) |  | 
		
			| Filter | : | Sintered |  | 
		
			| Measurement range | : | %0…100 L.E.L. |  | 
		
			| Protection grade | : | IP65 |  | 
		
			| Compliant with the following standards | : | 94/09/CE (ATEX)   89/336-92/31-93/68 (EMC) |  | 
		
			| Ex protection mode | : | EN 60079-1:1997+A1+A2   -  EN 60079-1:2000 |  | 
		
			| Performances | : | EN 60079-29-1:2000 |  | 
		
			| Electromagnetic compatibility | : | EN 50270:1999 |  | 
		
			| Software performances | : | EN 50271:2001 |  |