RYM02M_    2-4-8 ZONES CONTROL UNIT
                      
                    
	 
	
		
	
		 
	
		Microcontroller control unit capable of monitoring the gas concentration in to 2, 4 or 8 different zones (according to the product version): for each of these a 4 .. 20 mA transmitter can be wired for measurement and detection of either L.P.G., Methane, petrol vapors or Carbon Monoxide (CO).
	
		 
	
		 
	
		Technical features
		 
	
		
			
				| Power supply | : | 12...24 V or 100...240 V , 50..60 Hz | 
			
				| Versions | : | 2 / 4 / 8 outputs | 
			
				| Manages transmitters | : | CO, LPG, Methane (CH4) and Gas Vapors (n-octane) | 
			
				| Outputs | : | 1 Relay Pre-Alarm | 
			
				|  | : | 1 Relay Alarm 1 | 
			
				|  | : | 1 Relay Alarm 2 | 
			
				|  | : | 2 Relays auxiliary | 
			
				| Prealarm threshold range | : | adjustable 1…100% L.E.L. (LPG , methane and gas vapour) , 1…999 ppm (CO)
 | 
			
				| Alarm 1 threshold range | : | adjustable 1…100% L.E.L. (LPG , methane and gas vapour) , 1…999 ppm (CO)
 | 
			
				| Alarm 2 threshold range | : | adjustable 1…100% L.E.L. (LPG , methane and gas vapour) , 1…999 ppm (CO)
 | 
			
				| LED indicators | : | Green | active | 
			
				|  |  | Yellow | sensor failure | 
			
				|  |  | Yellow | current loop line failure (flashing) | 
			
				|  |  | Red | prealarm (flashing) | 
			
				|  |  | Red | alarm | 
			
				|  |  |  | 
			
				| Compliant with performance std | : | EN 60079-29-1: 2016 | 
			
				| ATEX Certificate | : | IMQ 20 ATEX 004 X | 
			
				| Protection grade | : | IP20 | 
		
	
 
	 
	 
	PRODUCT CODES
	40205/2...........RYM02M0  - 2 zones control unit
	40205/4...........RYM02M1  - 4 zones control unit
	40205/8...........RYM02M2  - 8 zones control unit